PlanaOS-P-Flo

PlanaOS-P-Flo flotation and filtration WWTP

PlanaOS-P-Flo industrial oil and oily wastewater treatment facilities are used to treat wastewater from industrial sites of oil and gas producing enterprises, refineries, energy and gas chemistry enterprises.

The basic purification technology is flotation followed by filtration.

  • Cleaning to fish farm standards
  • Block-modular design
  • Maximum factory readiness
  • Explosion and fireproof design (Ex)
  • Compliance with industry standards

Technologies PlanaOS-P PlanaNS-K

Constructions are carried out in a lightly prefabricated block or in a block-modular building equipped with all life support systems. Engineering and layout solutions provide convenient maintenance and access to equipment during maintenance and repair work.

PlanaOS-P-Flo industrial oil and oily wastewater treatment

* An example of a layout solution. The external storage tanks for raw effluent and the tank for clean/rinsing water are not shown conventionally.

PlanaOS-B-Flo installations can be made in a block-modular version for outdoor installation, or in a variant of installation in a production building.

Climatic version UHL, HL1 (when placed outdoors)
The material of the main structures Steel 09G2S
Enclosing structures Three-layer sandwich panels 150…250 mm
Process tanks and trays stainless steel
Technological pipelines PVC /PP / Stainless Steel / Carbon Steel
Performance 1…15 l/s
Number of lines From 1 to 3
Runoff averaging External storage tank
Basic technologies Oil recovery, reagent treatment, pressure flotation, mechanical and sorption filtration
Disinfection of drains UV disinfection
Disposal of treated effluents Under residual pressure / pressure
Sludge dewatering Screw-plate dehydrator
Reservation 100% hot reserve for drive equipment
Automation LSU based on a programmable logic controller
Operator’s workplace 15″ panel with mnemonic interface
KIP interfaces 4…20 mA, HART
Interfaces with the Customer’s automated control system RS 485 / Modbus RTU / Ethernet / Modbus TCP
Additional Spare parts, reagents and consumables for the period of the NDP

The plants provide wastewater treatment up to the indicators given in the table.

Indicator, mg/dm3 Input, max Output, no more
Suspended solids 500 3
Petroleum products 200 0.05
pH 7.0…11.0 7.0…8.5

The cost is determined by us in relation to your project, facility and wastewater quality.

At your request, we will provide a technical passport, a technological solution, a dimensional solution, bindings and loads, a commercial offer for the supply and provision of services.